The GDS 404 has been designed with features that provide an effective response to the detection of gas hazards in a wide range of environments, from commercial premises through to heavy industrial applications requiring hazardous area sensing. Typical monitor locations are public buildings, boiler plant rooms, swimming pools, water treatment works, H&V control systems, manufacturing and processing plants.
The GDS404+ is a wall or rack mounted control panel for one to four gas sensors, built up with plug-in channel cards. GDS lists public buildings, boiler plant rooms, swimming pools, water treatment works and process plants among typical locations, including sites that need hazardous area sensors. We supply, install, commission and service GDS404+ systems.
| Channels | 1 to 4 plug-in sensor channel cards |
|---|---|
| Gases | Combustible (LEL), toxic (ppm), oxygen depletion and enrichment, refrigerant |
| Sensor inputs | 3 wire mV bridge (catalytic); 2 or 3 wire 4 to 20mA |
| Relays | Common low, high, fault, over-range, global and inhibit; per channel low and high, 3A at 230V AC |
| Output | 4 to 20mA analogue |
| Power | 230/115V AC or 24V DC; optional 1 hour battery backup |
| Enclosure | Mild steel, IP52 (IP65 with over-housing), H265 x W315 x D95 mm |
| Standards | EMC BS EN 50270; low voltage BS EN 61010-1 |
We supply, install, commission and service this equipment across Ireland. Call 01 289 7720 or email info@vistec.ie for advice or a quote.
© 2026 Vistec Gas Detection Ltd

Descriptions