Gas interception automatic normally closed solenoid valves that open when the coil is powered and close when there is no voltage. They can be equipped with a flow regulator and adjustable slow opening kit.
Madas automatic solenoid valves are normally closed: they open the gas flow when the coil is powered and close it when power is removed. That makes them the shut-off point for a gas detection system, which cuts power to the valve on alarm. We supply, install, commission and service Madas valves on natural gas and LPG lines, matched to the panel and pipe size.
| Type | Automatic, normally closed (open when coil powered, closed without power) |
|---|---|
| Gases | Natural gas and LPG |
| Sizes | 1/4 inch (DN8) to 12 inch (DN300) |
| Maximum pressure | Versions from 0.2 bar to 6 bar, depending on model |
| Opening | Fast opening or slow opening versions |
| Protection | IP65 standard; ATEX versions for Zones 2 and 22, or Zones 1 and 2 |
| Options | Flow regulator, closed position indicator switch, open position indicator switch, visual closed position indicator |
| Standards | EN 161; EU type examination under Regulation (EU) 2016/426 (IMQ certificate 51BS3422) |
We supply, install, commission and service this equipment across Ireland. Call 01 289 7720 or email info@vistec.ie for advice or a quote.