The AGDS-2em v2 is designed for continuous monitoring across 2 channels with automatic safety control. It connects to low-voltage detectors for natural gas, LPG, carbon monoxide, carbon dioxide, or oxygen depletion, and provides automatic gas isolation in case of high alarm levels.
The Medem AGDS-2em v2 is a compact panel for one or two Medem detectors, designed mainly for boiler houses. On a high alarm it closes the connected gas control valve, and a fire alarm signal or emergency stop also shuts the gas off. We supply, install, commission and service the AGDS-2em with the matching valve and detectors.
| Gases | Natural gas, LPG, carbon monoxide, carbon dioxide, oxygen depletion |
|---|---|
| Detectors | 1 or 2 Medem low voltage detectors, pre-calibrated |
| Alarm levels | Combustible 5% LEL low, 10% LEL high; CO 20 ppm low, 30 ppm high; CO2 2800 ppm low, 5000 ppm high |
| Valve control | 230V output to the gas solenoid valve; closes on high alarm |
| Inputs | Panel emergency stop, remote emergency stop, fire alarm, thermal links |
| Outputs | Potential free BMS relay, mains rated, selectable alarm status |
| Power | 230V AC from a 3A fused spur |
| Enclosure | ABS, IP64, wall mounted |
We supply, install, commission and service this equipment across Ireland. Call 01 289 7720 or email info@vistec.ie for advice or a quote.
© 2026 Vistec Gas Detection Ltd

Descriptions